Categories

Advertising

Online Help

    Yahoo Messenger Online Help

Diesel Generator DP200P5S

Diesel Generator DP200P5S

DP200P5S

Perkins Engine

More details

General Specifications
Frequency(Hz): 50
Prime power(KVA(KW)): 200/164
Standby power(KVA(KW)): 220/176
Phase & wires: 3*4
Power factor: 0.8
Fuel: Diesel
Fuel consumption L/h(at 100% load): 46.5
Fuel consumption L/h(at 75% load): 34.9
Fuel tank capacity(L) : 250
Continuous runing hours(at 75% load): 7
Starting system: Electric

Specifications
- Engine
Model: 1106A-70TAG4
No. of cylinders: 6
Bore x stroke(mm): 105*135
Displacement(L): 7
Engine speed(rpm): 1500
Rated power(KW/BHP): 174/240
Lubrication oil(L): CH4/15W-40
Oil capacity(L): 16.5
Coolant capacity(L): 21
Governer method: ECM

- Alternator
Alternator model: LSA46.2M5
No. of poles: 4
Insulation(Hz): H
Voltage regulation(%): ±0.5
Excitation system: Brushless

- Soundproof Sets
Length: 3450
Width: 1150
Height: 1750
Approx net weight(Kg): 2960
Noise level(dBA@7m): TBD

- Open Sets
Model: DP200P5
Length: 2760
Width: 840
Height: 1550
Approx net weight(Kg): 1845
Fuel tank capacity: 330

Standard Features:
• Perkins engine
• Meccalte/Leroy Somer Altenator
• Excitation system: Self-excited
• Engine-mounted battery charging alternator
• Alternator IP23 protection, Canopy IP54 protection,Control system
• Stainless galvanized zinc plates with strong corrosion resistance
• Vibration isolators between the engine/Alternator and base frame
• Integrated wiring design
• Equipped with an industrial muffler
• Ambient Tempreature: -20°C to 50 °C. The coolant heater is needed when the temperature is below 5°C.
• 50°C Radiator
• High water temperature protection
• Low fuel level alarm
• 3 pole circuit breaker and power loom
• Neutral earth link
• Coolant and Lubricating Oil
• Drainage for fuel tank
• Top lifting and wooden pallet frame for forklift slots for 60kVA and below
• Steel base frame with top lifting and fork slots for 80kVA to 200kVA.
• Complete protection functions and safety labels

Optional Features:
• AMF controllers are optional for the generators standardized with Auto Gen controllers.
• AREP and PMG are optional
• ATS ( Automatic transfer switch)
• Sockets
• AMF controller
• Water jacket preheater, oil heater and double air cleaner, etc.
• 4 pole circuit breaker
• Automatic fueling system
• Fuel level switch
• Fuel transfer circuit